|
|
NAVSEA Code 00C manages the diver’s breathing air sampling program in
accordance with OPNAVINST 3150.27 (series). The purpose of the air sampling
program is to:
-
Provide technical support for the operation and maintenance of diver’s
breathing air compressors and diving air storage systems.
-
Provide general guidance concerning use of local commercial air sampling
sources, including the evaluation of commercial air sampling capabilities and
equipment.
-
Perform program management for centrally funded air sampling services as
directed by CNO Code N873D.
-
Collaborate with other government agencies and commercial industry on gas
purity standards and sampling procedures related to diver’s breathing gases.
Taking periodic air samples is a required maintenance
action and shall be performed in accordance with the PMS card(s)
applicable to the compressor or system producing diver’s breathing air. Each diver breathing-air source in service must be sampled approximately every 6 months
(within the interval between 4 and 8 months following the last accomplishment),
when contamination is suspected and after system overhaul.
Do not use a compressor that is suspected of producing contaminated air or that
has failed an air sample analysis until the cause of the problem has been corrected
and a satisfactory air sample analysis has been obtained validating the production
of acceptable air.
Diving systems that do not have a high-pressure (HP) air compressor within the
scope of certification shall only be charged with air produced by HP air compressors
listed on the ANU list and must have all applicable PMS completed up to
date, including air sample requirements. Examples of these types of systems
include MK 3 LWDS, Roper Cart, and various diving boats. HP banks on these
systems need not be sampled unless contamination is suspected.
Air drawn from submarine HP air storage banks for use as diver’s breathing air
shall be sampled in accordance with the PMS maintenance requirement card applicable
to the system, i.e., dry deck shelter system, submarine escape trunk, scuba
charging station. See paragraph 4-4.2 for additional information on system line-up
for sampling compressors where a sampling connection cannot be made immediately
downstream from the last air filtration device.
Table 4-1 shows the minimum purity requirements for diving air produced by
ANU-approved and certified diving air compressors. Air sampling services may
be procured locally from government or commercial air analysis facilities, or may
be acquired by utilizing analysis services coordinated via Coastal Systems Station
(CSS), Panama City, Florida.
NOTE |   | The most recent air sample analysis report shall be maintained on file for
each air compressor (by compressor serial number) used to produce
diver’s breathing air. |
The following general information is provided
to assist commands in managing air sample analysis programs.
Ensure all applicable PMS has been completed on the compressor and associated
filtration system prior to taking an air sample.
-
When sampling from HP charging systems, separate samples should be taken
from each compressor supplying the system. Samples from the compressors
should be taken as close to the compressor as possible but down stream of the
last compressor-mounted air treatment device (moisture separator, filter, etc.).
Some systems do not have fittings that allow samples to be taken from the
system at a location other than the charging connection. In this case, the
storage flasks should be isolated from the system, the system purged with air
from the compressor to be sampled and the sample taken at the charging
connection.
-
When sampling from a low-pressure (LP) breathing-air system, separate air
samples shall be taken from each LP compressor connected to the system.
Samples shall be taken from each LP compressor as close to the compressor as
possible, but downstream of the last compressor installed air treatment device
(moisture separator, filter, etc.). Some systems do not have fittings that allow
samples to be taken at connections other than the diver’s manifold. In this
case, a HP source should be isolated from the LP system, the system purged
with air from the LP compressor to be sampled, and the sample obtained from
the diver’s manifold.
NOTE |   | Failure to purge the system line-up of air produced from other
compressors or storage flasks will lead to an invalid air sample for the
compressor being sampled. |
-
Ensure that the compressor being sampled has reached full operating status
(proper operating temperature, oil pressure, and air pressure) and is properly
lined up to deliver air to the sample kit.
-
Ensure that the compressor’s intake is clear of any potential sources of
contamination (including consideration of ambient smog levels in areas where
smog is a problem).
-
Follow the procedures on applicable air sample MRC card.
-
Follow the instructions for operation of the air sampling kit.
The following applies to centrally funded air
sampling services coordinated by CSS. Due to limited funding, commands are
requested to schedule all compressors and associated samples to be taken at the
same time. CSS coordinates air sampling services with a commercial contractor.
Commands are not authorized to communicate directly with the commercial
contractor. Sampling services are provided at no cost to the command. To request
air sampling services, fill out and fax Air Sampling services request to COASTSYSTA
(Attn: Air Sampling). Telephone numbers are listed in Appendix 1C.
-
The user must provide the sample expiration date, the number and type (HP or
LP) of samples required, a complete mailing address, user point of contact and
phone number. Air sample kits will not be shipped until the required
information is received.
-
Allow a minimum of 5 working days after submitting a properly filled out
request form for delivery of a sampling kit in CONUS. Kits will be sent via
commercial air with a prepaid return mailer. Incomplete sample requests
cannot be acted on and will result in delay of shipping of sample kit.
-
Allow a minimum of 3 weeks after submitting a properly filled out request
form for delivery of a sampling kit if overseas. Kits will be sent via certified
priority mail for overseas/FPO-APO addressees with prepaid return mailing.
Incomplete sample requests cannot be acted on and will result in delay of
shipping of sample kit.
-
Detailed instructions are included with each sample kit. It is imperative to
follow those instructions and the instructions on the applicable compressor air
sampling MRC card.
-
Air samples shall be taken and returned to COASTSYSTA within 5 working
days of receipt of the air sample kit to preclude incurring late fees.
-
Air sample analysis reports for samples that meet air purity standards will be
mailed to the command. Commands will be notified by quickest means
possible, normally via fax, of any samples that do not meet minimum purity
requirements.
-
The user will be contacted immediately by phone and/or message by
COASTSYSTA if the sample fails to meet established purity standards. The
user will discontinue use of the air source until cause of contamination is
corrected. Corrective action must be taken prior to laboratory retest.
Commands may use local government (e.g., shipyards,
ship repair facilities, government research laboratories) or commercial
laboratories to analyze diver’s air samples. Commands are required to bear the
cost of locally procured air sample services. Local sampling facilities must be able
to analyze to U.S. Navy air purity standards.
|
|